Flexible Modular Redundancy
Single design
- The ET 200M I/O system
 |
The
ET 200M are mid-size, redundantly configurable, distributed
I/O subsystems, for the expansion of the SIMATIC safety controllers
via PROFIBUS.
An ET 200M station may contain both safe and standard I/O modules
and complies with the requirements of
SIL 3.
|
The ET 200M, like the other distributed I/Os of the ET
200 series, offers a redundant PROFIBUS communications capability.
Characteristic: modular I/O module for high-channel
applications, with up to 24 channels per module.
| Module |
Properties |
| SM 326 DI 24 DC24
V |
| - |
12 two-channel (SIL 3/Category 4) or 24 one-channel
(SIL 2) input |
| - |
Standard or fail-safe operation |
|
| SM 326 DO 10 DC24
V/2A |
| - |
10 P-P switching output channels SIL 3/Category
4 |
| - |
Standard or fail-safe operation |
|
| SM 336 AI 6 13 bits |
| - |
6 two-channel inputs |
| - |
4-20 mA |
|
| SM 326 DI 8 NAMUR |
| - |
4 two-channel inputs, SIL 3/Category 4 or 8 one-channel
inputs, SIL 2 for hazardous areas |
|
| Separate module |
| - |
For galvanic separation of fail-safe (critical)
and standard (non-critical) modules (SIL 3) |
|
The IM 153-2 and IM 153-2 FO interface modules can be
used for configuring redundant and safe stations.
|